Fire-water
systems shall be installed on petroleum Plant to cover the fire-water needs of
each plant. This document describes the minimum facilities and fire-water
capacities required to meet the statuary requirements.
The
permanent systems used for protection of equipment usually consist of a combination
of deluge, water sprays and fixed monitors.
·
A water deluge system is one in
which all the water is applied at the top of the vessel and allowed to run down
the sides.
·
A water spray system uses many
nozzles arranged in a grid pattern to distribute the water evenly over the
vessel.
·
Fixed monitors are permanently
connected to the fire-water grid system and directed at the protected unit.
Gas
turbines/compressors/expander packages are not water protected as the units are
enclosed and protected by CO2 total flooding systems.
All vessels
containing hydrocarbon liquids are water protected including their supporting
skirts.
Closed Drain Drum is
deluged as well as the Closed Drain Pump.
Compressor discharge
coolers are not water protected as those coolers are air cooler type and
contain little or no liquid.
Liquid filled coolers
are water protected; those with condensing liquids are not water protected.
The driver of the
Emergency Diesel Generator and its feed vessel will be deluged only if fire is
detected in its area. A dedicated deluge valve shall be provided for the skids.
Each LPG storage sphere
shall be protected either by a water deluge system or water spray system, to
protect against pool-fire exposure, supplemented by fixed monitors.
Fire-water Flow Rates
The minimum flow
rates used in determining the total fire-water flow rate are shown in Table
Flow is initiated only in the zone(s) where the fire is detected. In
the remaining zones, flow can be initiated manually. Fixed sprays or deluge
cover equipment and critical valves. Monitors and hydrants operation is manual.
The spray nozzle
shall be effective at the minimum discharge pressure given in NFPA 20 of 40
psig. In general spray nozzles are fully effectively from 50 psig upwards (3.5
barg).
For example: D3 Protect
spray Nozzle No. 21, K = 25.9 @ 3.5 barg
Q = Flow
rate, 48.5 litter/minute
P = Pressure,
bar
K = Nozzle
constant (by vendor)
Litters / minute
Contractor shall
fully design the actual fire-water network in detail engineering and all
assumed parameters in this document shall be recalculated to give the optimum
fire-water system.
Choosing a reliable LPG gas contractor is essential for a safe and efficient supply of liquefied petroleum gas.
ReplyDelete