12/3/14

INSTRUMENT ACCESSIBILITY TECHNICAL REQUIREMENTS

1.      Technical Requirements

All materials and equipment furnished shall be new, un­used and free of defects.  Materials and equipment shall be protected from construction damage, particularly damage due to sandblasting and painting. Each instrument furnished shall be provided with fully completed data sheets.  Data Sheets shall be numbered and indicate manufacturer and model numbers. Stan­dard ISA instrument data sheets will be acceptable.
Multiple listing of instruments on one sheet is permitted; however, they must be arranged in numerical sequence by tag number.  Only identical instruments may be listed on each data sheet i.e. the only difference allowed is tag numbers. An assigned tag number which is cancelled due to instru­ment revisions shall not be re-used.
Where possible, the instrument selection shall represent the man­ufacturer's standard.  Standardization of instru­ments types, manufacturer, and model shall be considered for the purpose of simplifying design and reducing spare parts. Selection of instruments and supporting hardware shall be made with consideration of the process fluid, the operat­ing environment, and the electrical area classification. Process fluids, steam or water shall not be channeled into control rooms for direct measurements.
Instrument pneumatic analog signals shall be 3 - 15 psig, un­less otherwise specified or required by the equipment such as valve operators.  Instrument pneumatic on-off signals shall generally be 30 psig. Pneumatic instruments requiring a regulated air supply shall be furnished with a SS 316 filter regulator and output gauge of SS 316.
The use of transmitters shall be maximized to improve overall reliability and availability. All transmitters shall be “SMART” electronic type utilizing ‘dual mode’ output with 2 wire 4 – 20 mA signal with superimposed ‘HART’ protocol communication signal.
Local electric control switches shall be DPDT, unless oth­erwise specified. Discrete (On-off) electric signals shall be 24 VDC unless otherwise specified. Use of local electronic control switches in lieu of electronic type transmitters requires Company approval. Separate instruments along with separate piping and vessel tapping / connections shall be used for shutdown initiating devices.
Where two (2) pressure or temperature transmitters monitor the same parameter then local gauge need not be provided. The control transmitter installation is to include a plugged connection where a gauge can be added at future time. Instrument stands shall be designed to accommodate the future gauge. Each field and control panel instrument shall have a per­manent SS 316 nameplate bearing its tag number. Tag num­bers shall be stamped and not engraved.

2.      Instrument Accessibility

Each instrument shall be considered as a normal working location and therefore shall be properly located in order to satisfy workers safety conditions as well as efficiency. Instrument accessibility being able to induce heavy consequence on piping or complex layout, this problem shall be considered as soon as possible during the detailed engineering stage.
It shall be important to distinguish two kinds of working location:
a.     Permanent working location
b.    Non permanent working location.
A working location shall be considered as permanent when visit frequency is higher than once a week. Non permanent working location shall have visit frequency lower than once a week. For permanent type, the access shall be easy. Access platforms are to be provided where applicable and movable ladders not permitted. For non-permanent type, movable ladders shall be allowed if height is less than 3 meters.
The following instruments and accessories shall be considered as permanent working location:
Control valves, ON / OFF actuated valves, transmitters, local controllers, local converters, in-line flow meters, level gages, level switches, pressure switches, temperature elements (indication and control) with transmitters, analyzer take off point, sampling loop.
The following instruments shall be considered as non -permanent working location: orifice flanges, pressure taps, thermocouples or RTD’s, and thermo well. Permanent access at these locations is not required.

3.      Instruments Process Connections

When an instrument is connected to the process by means of flanges, those flanges shall be ANSI 150# RF rated as a minimum. The following Table-1 gives the main requirements concerning instrument taps/nozzles.
TABLE–1
 
Note:
1.     To be confirmed with TW stress calculations, 2½" flange is not allowed due to piping class constraint.
Minimum insertion length of thermo wells shall be that of 4” pipe expander/reducers as indicated on the P&ID’s.
2.     A 2 x 3” expander shall be provided.

No comments:

Post a Comment

MATERIAL AND EARTH WORK SPECIFICATION

Borrow Material Borrow material shall meet the requirement specified for satisfactory fill materials per ASTM D2487 or ASTM D...